Logging

The Data, Energy, Waveform, and Trigger Data logs support sequential record
retrieval but require additional configuration steps. See

Energy Log on page 109

,

Waveform Log (M6 Model) on page 105

,

Data Log on page 113

, and

Trigger

Data Log (M6 model) on page 145

for more information.

To initiate this type of log retrieval, a controller or application sets parameter
values in the Configuration.Log_Read table, writes the table to the power
monitor, and then reads the applicable LoggingResults table.

Refer to the

Communication

chapter for more information.

Selected Log

Selects the log from which to retrieve information. Once a single request has been
made the auto, or sequential, return feature brings back successive records each
time the log is read. Some logs support individual record requests. In the case of
the Data, Energy, Waveform, and Trigger Logs, the data returned are file names of
the log files. These are the choices.

Requests not supported by the power monitor model are ignored.

Chronology of Auto Return Data

Selects the chronological order of sequentially retrieved records. This parameter
is ignored if a specific record is requested from the Min/Max, Load Factor, or
TOU log. These are the choices:

0 = Reverse direction (most recent record first)
1 = Forward direction (oldest record first)

IMPORTANT

Sequential record retrieval is available for networks such as DeviceNet that do
not support ftp. Download speed and performance by using sequential record
retrieval is significantly lower than if using ftp.

Parameter Value

Results Table

1 = Event Log

LoggingResults.Event_Log (sequential only)

2 = Min/Max Log

LoggingResults.MIN_MAX_Log

3 = Load Factor Log

LoggingResults.LoadFactor_Log

4 = Time of Use Log

LoggingResults.TOU_Log

5 = Setpoint Log

LoggingResults.Setpoint_Log (sequential only)

6 = Alarm Log

LoggingResults.Alarm_Log (sequential only)

7 = Data Log FIle List

LoggingResults.DataLog_FileName

8 = Energy Log File List

LoggingResults.EnergyLog_FileName

9 = Trigger Data File (M6)

LoggingResults.TriggerLog_FileName

10 = Power Quality Log (M6)

LoggingResults.PowerQuality_Log

11 = Waveform Log File (M6)

LoggingResults.WaveformFileName