Commands – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 147

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

147

Logging

Chapter 6

3.

Read the trigger data setpoint information file name from the

LoggingResults. TriggerLog_Setpoint_Info_File_Name (M6 model)

table

one or more times until the desired file name is returned.

4.

Read the trigger data file name from the

LoggingResults.TriggerLog_FileName Data Table

one or more times until

the desired file name is returned.

5.

Write the selected file names into the

Configuration.TriggerDataLogFile

(M6 Model)

and

Configuration.TriggerSetpointInfoFile (M6 model)

tables.

6.

Perform a read of the

LoggingResults.TriggerData_Header (M6 model)

table and store the results in a suitable location.

7.

Perform sequential reads of the

LoggingResults.TriggerData_Log (M6

model)

table and store the results in a suitable location.

The first read returns the total number of cycle data records in the log
along with the selected parameter ID numbers. Subsequent reads return
each the value of the selected parameters, cycle-by-cycle.

Commands

Clear trigger data log (Command Word 2 = 13)