Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

233

PowerMonitor 5000 Unit Data Tables

Appendix A

Configuration.Instance

Table 43 - Table Properties

CIP

102

No. of Elements

43

Length in Words

80

Data Type

Varies

Data Access

Read/Write

Table 44 - Configuration.Instance Data Table

Start
Byte

Size Type

Tag

Name

Description

Units

Range

0

1

SINT

MeterMode

Configures the input wiring for metering.
0 = Demo
1 = Split Phase
2 = Wye
3 = Delta 2 CT
4 = Delta 3 CT
5 = Open Delta 2 CT
6 = Open Delta 3 CT
7 = Delta Gnd B Ph 2 CT
8 = Delta Gnd B Ph 3 CT
9 = Delta High Leg

Mode

0…9

1

SINT

Pad01

For alignment purpose

INT

Pad02

For alignment purpose

4

4

Real

VLinePTPrimary

The primary voltage value of the PT transformer

V

0…1,000,000

8

4

Real

VLinePTSecondary

The secondary voltage value of the PT transformer

V

0…690

12

4

Real

ILineCTPrimary

The primary ampere value of the CT transformer

A

0…1,000,000

16

1

SINT

ILineCTSecondary

The secondary ampere value of the CT transformer

A

5

1

SINT

Pad03

2

INT

Pad04

For alignment purpose

20

4

Real

VNPTPrimary

The primary voltage value of the PT transformer

V

0…1,000,000

24

4

Real

VNPTSecondary

The secondary voltage value of the PT transformer

V

0…690

28

4

Real

I4CTPrimary

The primary ampere value of the CT transformer

A

0…1,000,000

32

1

SINT

I4CTSecondary

The secondary ampere value of the CT transformer

A

5

1

SINT

Pad05

For alignment purpose

2

INT

Pad06

For alignment purpose

36

4

Real

NominalVToVVoltage

Nominal voltage value or voltage rating of the system being metered.

V

0…1,000,000

40

4

DINT

Pad07

For alignment purpose

N/A

0…0

44

4

Real

NominalFreq

Nominal frequency of the system.
50=50 Hertz
60=60 Hertz

Hertz

50 or 60