Configuration.TriggerSetpointInfoFile (M6 model)

Configuration.TriggerData(M6 model)

Table 89 - Table Properties

CIP Instance Number

865

PCCC File Number

ST74

No. of Elements

1

Length in Words

32

Data Type

String

Data Access

Write Only

Table 90 - Configuration.TriggerSetpointInfoFile Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

String

Trigger_Setpoio
nt_Log_File

A single entry table for a 64 character Filename entry

0

64 bytes

Table 91 - Table Properties

CIP Instance Number

822

PCCC File Number

N31

No. of Elements

10

Length in Words

10

Data Type

Int16

Data Access

Read/Write

Table 92 - Configuration.TriggerData Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Int16

Trigger_Mode

Selects how records are saved. 0= Fill and stop recording when log is full. 1= Overwrite
when log is full starting with the earliest record.

1

0…1

1

Int16

TriggerData_Length_s

TriggerData log length from 1s to 10s

1s

1…10s

2

Int16

TriggerData_Parameter_1

Selection of parameter or default to be logged in the trigger data log.

5

1…184

3

Int16

TriggerData_Parameter_2

9

1…184

4

Int16

TriggerData_Parameter_3

14

1…184

5

Int16

TriggerData_Parameter_4

15

1…184

6

Int16

TriggerData_Parameter_5

19

1…184

7

Int16

TriggerData_Parameter_6

23

1…184

8

Int16

TriggerData_Parameter_7

27

1…184

9

Int16

TriggerData_Parameter_8

39

1…184

Advertising