Status.discreteio – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 296

Advertising
background image

296

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

Status.DiscreteIO

Table 107 - Table Properties

CIP Instance Number

826

PCCC File Number

N35

No. of Elements

112

Length in Words

112

Data Type

Int16

Data Access

Read Only

Table 108 - Status.DiscreteIO Data Table

Element
Number

Type

Tag Name

Description

Range

0

Int16

Status_Input_States

Indicates the overall Status Input Condition

65,535

Bit 0

Status_Input_1_Actuated

Indicates Status 1 actuated

0 or 1

Bit 1

Status_Input_2_Actuated

Indicates Status 2 actuated

0 or 1

Bit 2

Status_Input_3_Actuated

Indicates Status 3 actuated

0 or 1

Bit 3

Status_Input_4_Actuated

Indicates Status 4 actuated

0 or 1

Bit 4

KYZ _Output_Energized

Indicates Output KYZ Energized

0 or 1

Bit 5

KYZ_Forced_On

Software Control Forced On KYZ

0 or 1

Bit 6

KYZ_Forced_Off

Software Control Forced Off KYZ

0 or 1

Bit 7

Relay_1_Output_Energized

Indicates Output Relay 1 Energized

0 or 1

Bit 8

Relay_1_Forced_On

Software Control Forced On Relay 1

0 or 1

Bit 9

Relay_1_Forced_Off

Software Control Forced Off Relay 1

0 or 1

Bit 10

Relay_2_Output_Energized

Indicates Output Relay 2 Energized

0 or 1

Bit 11

Relay_2_Forced_On

Software Control Forced On Relay 2

0 or 1

Bit 12

Relay_2_Forced_Off

Software Control Forced Off Relay 2

0 or 1

Bit 13

Relay_3_Output_Energized

Indicates Output Relay 3 Energized

0 or 1

Bit 14

Relay_3_Forced_On

Software Control Forced On Relay 3

0 or 1

Bit 15

Relay_3_Forced_Off

Software Control Forced Off Relay 3

0 or 1

1…55

Int16

Reserved

Future Use

0