Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

179

Other Functions

Chapter 8

Reset (default)

Reset performs a warm restart of the power monitor firmware. With Reset
selected for unit error action, if a critical error occurs, the power monitor logs the
error record to its internal Error Log and then restarts automatically. With Reset
selected for the error log full option, the oldest error log record is discarded, and
then the power monitor logs the error record to its internal Error Log and then
restarts automatically. This option is intended for applications where continuity
of metering operation is paramount, and where critical control functionality
cannot be affected by an operating error in the power monitor.

Safe Mode

In Safe mode each power monitor output is forced to its de-energized state, native
Ethernet communication stops, and the power monitor enters a state of minimal
functionality. In safe mode, you can access the unit’s Safe mode web page through
the USB device port. The Safe mode web page displays the following:

Links for downloading error and warning logs

Control buttons to clear diagnostic logs and reset the unit

From Safe Mode, if the error log is full, you need to clear the error log before
attempting to reset the unit.

Contact Rockwell Automation Technical Support for assistance with the
PowerMonitor 5000 unit diagnostic information.

Setup

Setup parameters of these functions are in the

Configuration.System.General

table.