Waveform data records – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 107

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

107

Logging

Chapter 6

Waveform Data Records

The LoggingResults.Waveform_Log table contains the most recent record read
from the selected waveform file, and contains the following REAL elements.

Element Number

Tag Name

Description

0

Record_Indicator

Indicates the significance of the data in the record

0 = No record returned
1 = the record contains parameter values
2 = the record contains general information of the log file being retrieved, reference to each item
description in the data table;
3 = log file not found.

1

Timestamp_Date

Date of cycle collection MMDDYY

2

Timestamp_Time

Time of cycle collection hhmmss

3

Microsecond_Stamp

Microsecond of cycle collection

4

File_ID

The selected file ID

5

Total_Cycles

Total cycles of the waveform file

6

Cycle_Returned

The current returned cycles

7

Frequency

The frequency of average cycle

8

Mag_Angle

The returned value is magnitude or angle

9

Channel

The channel returned

10

Order

The order of returned values

11

X_(0 + Order * 32)

The returned value X_(h) where X_(h) = the RMS magnitude or angle of the spectral component h. Units are
Volts, Amps or degrees, depending on the value of Channel and Mag_Angle elements

12

X_(1 + Order * 32)

42

X_(31 + Order * 32)

Advertising