Appendix A

PowerMonitor 5000 Unit Data Tables

Status.Communications

Table 103 - Table Properties

CIP Instance Number

824

PCCC File Number

N33

No. of Elements

61

Length in Words

61

Data Type

Int16

Data Access

Read Only

Table 104 - Status.Communications Data Table

Element
Number

Type

Tag Name

Description

Range

0

Int16

Ethernet_Overall_Status

Ethernet Communication Overall Status
0 = Pass
1…32766 = Fail

0…32,766

bit 0

IP_and_Subnet

Invalid IP Address or Subnet Mask
0 = PASS
1 = FAIL

0 or 1

bit 1

Gateway_Address

Invalid Gateway Address
0 = PASS
1 = FAIL

0 or 1

bit 2

DNS_Server_Address

Invalid DNS server Address
0 = PASS
1 = FAIL

0 or 1

bit 3

DNS_Server2_Address

Invalid DNS server2 Address
0 = PASS
1 = FAIL

0 or 1

bit 4

SNTP_Server_Address

Invalid Timer Server Address
0 = PASS
1 = FAIL

0 or 1

bit 5

DHCP_Server_Timeout_Test

DHCP Server Timeout
0 = PASS
1 = FAIL

0 or 1

bit 6

Duplicate_IP_Address_Test

Duplicate IP Address
0 = PASS
1 = FAIL

0 or 1

bit 7

Time_Server_Timeout_Test

Time Server Timeout
0 = PASS
1 = FAIL

0 or 1

bit 8

DNS_Server_Timeout_Test

DNS Server Timeout
0 = PASS
1 = FAIL

0 or 1

bit 9…15

Reserved

Future Use

0

1…60

Int16

Reserved

Future Use

0