Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

48

1

SINT

RealTimeUpdateRate

Selects the update rate for the realtime table and the setpoint
calculations.
0 = Single cycle averaged over 8 cycles
1 = Single cycle averaged over 4 cycles
2 = 1 cycle with no averaging
3 = 200 ms per EN61000-4-30 (M6 and M8 Only)

Meter
Averaging

0…3

1

SINT

Pad08

For alignment purpose

2

INT

Pad09

For alignment purpose

52

2

INT

DeviceFaultAction

This parameter determines the action when a unit error occurs.
0 = Halt on error and make status indicator solid red
1 = Reset power monitor hardware

Error Action

0…1

54

2

INT

EnergyLogInverval

Selects how often a record is logged (minutes). A value of 0 disables
periodic logging of records. A value of -1 causes the logging of records
to be synchronized to the end of the demand Interval.

Energy Interval
(Minutes)

-1…60

56

2

INT

EnergyLogMode

This parameter sets the action of the log once it has filled to capacity.
0 = Fill and Stop
1 = Overwrite oldest record.

Energy Log
Mode

0…1

58

2

INT

TOU AutoStoreDay

Automatically stores the current record for the month replacing an
older record if the log is full. The log holds 12 records plus the current
record.
0 = Disable storing records
1 = Store and clear on the first day of the month
2 = 2nd of month
3 = 3rd day of month

31 = 31st day of month
If set to 29…31 the last day of every month stores a record.

AutoStore

0…31

60

1

SINT

DemandSource

When item ‘Demand Broadcast Master Select’ of the Ethernet table is
set to a master selection of 0…2 sets the type of master input. In this
case item ‘3’ is ignored. When the ‘Demand Broadcast Master Select’
of the Ethernet table is set to slave, then any of these inputs can set
the end of the demand period.
0 = Internal Timer
1 = Status Input 2
2 = Controller Command
3 = Ethernet Demand Broadcast

Demand Period
Length

0…3

1

SINT

Pad10

For alignment purpose

2

INT

Pad11

For alignment purpose

64

1

SINT

DemandPeriodLength

Specifies the desired period for demand calculations. When set to 0
there is no projected demand calculations. If the internal timer is
selected a setting of 0 turns the demand function off.

Number
Demand
Periods

0…99

1

SINT

Pad12

For alignment purpose

2

INT

Pad13

For alignment purpose

68

1

SINT

NumberOfDemandCycles

Specifies the number of demand periods to average for demand
measurement.

Demand Sync
Delay

1…15

1

SINT

Pad14

For alignment purpose

2

INT

Pad15

For alignment purpose

Table 44 - Configuration.Instance Data Table

Start
Byte

Size Type

Tag

Name

Description

Units

Range