Set this command word value to execute the corresponding action. These are the
selections:

10 = Force KYZ Output On
11 = Force KYZ Output Off
12 = Remove Force from KYZ
13 = Force Relay 1 Output On
14 = Force Relay 1 Output Off
15 = Remove Force from Relay 1
16 = Force Relay 2 Output On
17 = Force Relay 2 Output Off
18 = Remove Force from Relay 2
19 = Force Relay 3 Output On
20 = Force Relay 3 Output Off
21 = Remove Force from Relay 3

Related Functions

Configuration lock

Status Log

Setpoints

EDS add-on profile

Status Inputs

The PowerMonitor 5000 unit has four self-powered (24V DC) status inputs.
Two typical uses for status inputs are to totalize external pulse meters and to
synchronize the demand end of interval (EOI).

Applications

This applies to all models.

Operation

Each time status input 1 sees an off to on transition, the status input 1 scale factor
is added to the status input 1 count. The count continues to increase, rolling over
to zero at a value of 9,999,999,999,999 (10

13

– 1). Status input 2, 3 and 4 operate

in the same fashion. The status input 2 counter operates whether or not the input
is used for demand EOI synchronization.

Setup

The setup parameters for pulse totalizing and scaling are in the

Configuration.System.General

table and are summarized below.