Loggingresults.triggerdata_header (m6 model), Loggingresults. triggerdata_header data table – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 347

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

347

PowerMonitor 5000 Unit Data Tables

Appendix A

LoggingResults.TriggerData_Header (M6 model)

Table 165 - Table Properties

CIP Instance Number

862

PCCC File Number

F71

No. of Elements

15

Length in Words

30

Data Type

Real

Data Access

Read Only

Table 166 - LoggingResults. TriggerData_Header Data Table

Element
Number

Type

Tag Name

Description

Unit

Range

0

Real

Record_Indicator

Indicates the significance of data in the record

0 = No record returned
1= the record contains
parameter values
2 = the record contains general
information of the log file being
retrieved, reference to each item
description in the data table
3= log file not found

1

Real

TriggerHeader_Record
_Identifier

Internal unique record number, if Record_Indicator = 1
Total records number in the log file, if Record_Indicator = 2.

#

+/- 0…9.999E15

2

Real

TriggerAction_
Timestamp_Year

The year when the trigger action occurred.

YYYY

2010…2100

3

Real

TriggerAction_
Timestamp_Month_
Day

The month and day when the trigger action occurred.

MMDD

0110…1231

4

Real

TriggerAction_
Timestamp_Hour_
Minute

The hour and minute when the trigger action occurred.

hhmm

0000…2359

5

Real

TriggerAction_
Timestamp_Sec_mS

The seconds and milliseconds when the trigger action occurred.

ssmS

00000…59999

6

Real

SetpointNumber

Setpoint number of trigger

#

1…30

7

Real

ParameterSelection or
Logic_Gate_Type

ParameterSelection if SetpointNumber = (1…20)
Logic_Gate_Type if SetpointNumber = (21 …30)

#

See description

8

Real

ReferenceValue or
Logic_Input_1

ReferenceValue if SetpointNumber = (1…20)
Logic_Input_1 if SetpointNumber = (21… 30)

#

See description

9

Real

TestCondition or
Logic_Input_2

TestCondition if SetpointNumber = (1…20)
Logic_Input_2 if SetpointNumber = (21 …30)

#

See description

10

Real

EvaluationType or
Logic_Input_3

EvaluationType if SetpointNumber = (1…20)
Logic_Input_3 if SetpointNumber = (21…30)

#

See description

11

Real

Threshold or
Logic_Input_4

Threshold if SetpointNumber = (1… 20)
Logic_Input_4 if SetpointNumber = (21… 30)

#

See description

12

Real

Hysteresis

Hysteresis for setpoint

#

0…10,000,000

13

Real

AssertDelay_s

AssertDelay for setpoint

s

0.000…3600

14

Real

DeassertDelay_s

DeassertDelay for setpoint

s

0.000…3600

Advertising