Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 304

Advertising
background image

304

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

6

Int16

Logs_Status

Logs Condition Status

0… 65,535

Bit 0

Data_Log_Full_Fill_And_Stop

Is Set when fill and stop is configured and log is at least 80% filled

0…1

Bit 1

Event_Log_Full_Fill_And_Stop

Is Set when fill and stop is configured and log is at least 80% filled

0…1

Bit 2

Setpoint_Log_Full_Fill_And_Stop

Is Set when fill and stop is configured and log is at least 80% filled

0…1

Bit 3

PowerQuality_Log_Full_Fill_And_Stop

Is Set when fill and stop is configured and log is at least 80% filled

0…1

Bit 4

Energy_Log_Full_Fill_And_Stop

Is Set when fill and stop is configured and log is at least 80% filled

0…1

Bit 5

Waveform_Full

Is Set when log is at least 80% filled

0…1

Bit 6

TriggerData_Full_Fill_And_Stop

Is Set when fill and stop is configured and log is at least 80% filled

0…1

Bit 7…15

Reserved

Reserved for future use

0

7

Int16

Output_Pulse_Overrun

The output pulse rate exceeds the configured capability

0

Bit 0

KYZ_Pulse_Overrun

The KYZ output pulse rate exceeds the configured capability

Bit 1

Relay1_Pulse_Overrun

The Relay 1 output pulse rate exceeds the configured capability

Bit 2

Relay2_Pulse_Overrun

The Relay 2 output pulse rate exceeds the configured capability

Bit 3

Relay3_Pulse_Overrun

The Relay 3 output pulse rate exceeds the configured capability

Bit 4…15

Reserved

Reserved for future use

8

Int16

IEEE1159_Over_Voltage

Over Voltage Condition

0…65535

Bit 0

IEEE1159_Over_Voltage_V1

1 = An over voltage is detected on V1

0…1

Bit 1

IEEE1159_Over_Voltage_V2

1 = An over voltage is detected on V2

0…1

Bit 2

IEEE1159_Over_Voltage_V3

1 = An over voltage is detected on V3

0…1

Bit 3... 15

Reserved

Reserved for future use

0

9

Int16

IEEE1159_Under_Voltage

Under Voltage Condition

0…65535

Bit 0

IEEE1159_Under_Voltage_V1

1 = An under voltage is detected on V1

0…1

Bit 1

IEEE1159_Under_Voltage_V2

1 = An under voltage is detected on V2

0…1

Bit 2

IEEE1159_Under_Voltage_V3

1 = An under voltage is detected on V3

0…1

Bit 3... 15

Reserved

Reserved for future use

0

10

Int16

IEEE1159_Imbalance_Condition

IEEE1159 Imbalance

0…65535

Bit 0

IEEE1159_Imbalance_Condition_Volts

1 = An Imbalance is detected on Voltage

0…1

Bit 1

IEEE1159_Imbalance_Condition_Current

1 = An Imbalance is detected on Current

0…1

Bit 2...15

Reserved

Reserved for future use

0

11

Int16

IEEE1159_DCOffset_Condition

IEEE1159 DC Offset Condition

0…65535

Bit 0

IEEE1159_DCOffset_Condition_V1

1 = A DC offset exceed limitation is detected on V1

0…1

Bit 1

IEEE1159_DCOffset_Condition_V2

1 = A DC offset exceed limitation is detected on V2

0…1

Bit 2

IEEE1159_DCOffset_Condition_V3

1 = A DC offset exceed limitation is detected on V3

0…1

Bit 3... 15

Reserved

Reserved for future use

0

12

Int16

IEEE1159_Voltage_THD_Condition

IEEE1159 Voltage THD Condition

0…65535

Bit 0

IEEE1159_Voltage_THD_Condition_V1

1 = A THD exceed limitation is detected on V1

0…1

Bit 1

IEEE1159_Voltage_THD_Condition_V2

1 = A THD exceed limitation is detected on V2

0…1

Bit 2

IEEE1159_Voltage_THD_Condition_V3

1 = A THD exceed limitation is detected on V3

0…1

Bit 3... 15

Reserved

Reserved for future use

0

Table 116 - Status.Alarms Data Table

Element
Number

Type

Tag Name

Description

Range