Configuration parameter object table – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 238

Advertising
background image

238

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

Configuration Parameter Object Table

Table 45 - Table Properties

CIP Class Code

0x0F

No. of Parameters

52

Data Type

Varies

Data Access

Read/Write

TIP

Refer to

Table 44

Configuration.Instance Data Table

for descriptions of each

parameter.

Table 46 - Configuration Parameter Object Table

Instance Number

Parameter Object Name

Type

Units

Range

Default Value

1

Metering_Mode

Real

N/A

0…9

2

2

V1_V2_V3_PT_Primary

Real

V

0 …1,000,000

480

3

V1_V2_V3_PT_Secondary

Real

V

0…690

480

4

I1_I2_I3_CT_Primary

Real

A

0…1,000,000

5

5

I1_I2_I3_CT_Secondary

Real

A

5

5

6

VN_PT_Primary

Real

V

0 …1,000,000

480

7

VN_PT_Secondary

Real

V

0…690

480

8

I4_CT_Primary

Real

A

0…1,000,000

5

9

I4_CT_Secondary

Real

A

5

5

10

Nominal_System_LL_Voltage

Real

V

0…1,000,000

480

11

Reserved

Real

N/A

0…0

0

12

Nominal_System_Frequency

Real

Hz

50…60

60

13

Realtime_Update_Rate

Real

N/A

0…3

0

14

Date_Year

Int16

Year

2010…2100

2010

15

Date_Month

Int16

Mon

1…12

1

16

Date_Day

Int16

Day

1…31

1

17

Time_Hour

Int16

Hour

0 …23

0

18

Time_Minute

Int16

Min

0…59

0

19

Time_Seconds

Int16

Sec

0…59

0

20

Time_Milliseconds

Int16

Mise

0…999

0

21

Unit_Error_Action

Int16

N/A

0…1

1

22

Energy_Log_Interval

Int16

N/A

-1…60

15

23

Energy_Log_Mode

Int16

N/A

0…1

1

24

Time_Of_Use_AutoStore

Int16

N/A

0…31

31

25

Demand_Source

Real

N/A

0… 3

0

26

Demand_Period_Length

Real

N/A

0…99

15

27

Number_Demand_Periods

Real

N/A

1…15

1

28

Forced_Demand_Sync_Delay

Real

N/A

0…900

10

Advertising