Devicenet and controlnet object model, Object class list, Explicit messaging – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 188

Advertising
background image

188

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Chapter 9

Communication

DeviceNet and ControlNet
Object Model

This section provides the object model for a PowerMonitor 5000 device type on
either a DeviceNet or ControlNet network. The table below indicates the
following:

The object classes present in this device

Whether or not the class is required

The number of instances present in each class

Object Class List

The PowerMonitor 5000 unit supports the following classes.

Explicit Messaging

This section discusses data retrieval and parameter configuration by using explicit
messaging from Rockwell Automation controllers. Explicit messaging provides
the mechanism for users to program a controller to read and write specific data
tables in a power monitor. With explicit messages, users can read real-time
metering values, configure metering and communication parameters, and also
read certain logs.

The PowerMonitor 5000 unit supports PLC-5 Typed, SLC Typed, and CIP
Generic message requests.

Table 33 - DeviceNet and ControlNet Object Model

Object Class

Need in Implementation

Number of Instances

Identity (1, 1hex)

Required

1

Message Router (2, 2hex)

Required

1

DeviceNet Object (3, 3hex)

Required

1

Assembly Object (4, 4 hex)

Required

Minimum of 3

Connection Object (5, 5hex)

Required

Minimum of 1

Parameter Object (15, Fhex)

Required

Product Specific

Parameter Group Object (16, 10hex)

Optional

Product Specific

Acknowledge HandleObject (43, 28hex)

Required

1

Non-Volatile Storage Object (161, A1hex)

Required

Product Specific

File Object (55, 37hex)

Required

Minimum of 1

PCCC Object (103, 67hex)

Optional

1

Energy Object (78, 4Ehex)

Required

1

Electrical Energy Object (79, 4Fhex)

Required

1

Email Object (815, 32Fhex)

Optional

1