Table 193 - Input and Output Ratings

Parameter

Rating

Voltage Sense Inputs: V1, V2, V3, VN

Input Impedance: 5M ohm min
Input current: 1 mA max

Current Sense Inputs: I1, I2, I3, I4

Overload Withstand: 22 A Continuous, 200 A for one
second
Burden: Negligible
Impedance: Negligible
Maximum Crest Factor at 5 A is 4.0
Starting Current: 5 mA

Status Inputs

Contact Closure (Internal 24V DC)

KYZ Output

Solid State KYZ: 80 mA at 240V AC/V DC

Control Relay

ANSI C37.90 trip duty: 2005

Table 194 - Control Relay

Rating

50/60 Hz AC RMS

DC

Max Resistive Load Switching

10 A at 240V
(2400VA)

10 A at 24V and
0.25 A at 125V

Min Load Switching

100 mA at 5V

10 mA at 5V

UL 508, CSA 22.2, IC Rating Class

B300

Q300

Max Make Values (Inductive Load)

30 A at 120V
15 A at 240V (3600VA)

0.55 A at 125V
0.27 A at 240V (69VA)

Max Break Values (Inductive Load)

3 A at 120V
1.5 A at 240V (360VA)

0.55 A at 125V
0.27 A at 240V (69VA)

Max Motor Load Switching

1/3 HP at 125V
1/2 HP at 240V