Install the PowerMonitor 5000 Unit

Chapter 2

Voltage Sensing

Circuits rated up to 690V AC line-to-line can be connected directly. Higher
voltages require potential transformers (PTs), also known as voltage transformers
(VTs), to step the voltage down.

Wiring must conform to all applicable codes and standards. In particular, suitable
overcurrent protection must be provided by the user, with current and
interrupting ratings selected to protect the wiring.

Pay particular attention to correct phasing and polarity of voltage connections.
The diagrams use the ‘dot’ convention to indicate transformer polarity. The dot
indicates the H1 and X1 terminals on the high side and low side of the
transformer respectively.

When wiring a PowerMonitor 5000 unit to existing PTs and metering devices,
the voltage sensing terminals of the PowerMonitor 5000 unit must be connected
in parallel with the voltage sensing terminals of the existing metering devices.

Table 5 - Selecting Wiring Diagrams and Metering Modes

Circuit Type

Line - Line Voltage

No. of CTs

No. of PTs

Voltage Sensing

Current Sensing

Metering_Mode

3-phase, 4-wire Wye

≤690 V

3

-

Diagram V1

Diagram I3

Wye

> 690 V

3

Diagram V3

3-phase, 3-wire
grounded Wye

≤690 V

-

Diagram V2

> 690 V

3

Diagram V5

3-phase, 4-wire
impedance grounded
Wye

≤690 V

-

Diagram V1

> 690 V

3 L-N

Diagram V3

3 L-N, 1 N-G

Diagram V4

3-phase, 3-wire Delta
or ungrounded Wye

≤690 V

2

-

Diagram V2

Diagram I2

Delta 2 CT

3

Diagram I3

Delta 3 CT

> 690 V

2

2

(3)

Diagram V6

Diagram I2

Open Delta 2 CT

3

Diagram I3

Open Delta 3 CT

Split-phase/Single-
phase

(1)

≤690 V

2/1

-

Diagram V7

Diagram I1

Split-phase

> 690 V

2/1

2/1

Diagram V8

3-phase, 3-wire Delta,
Grounded B Phase

(2)

≤690 V

2

-

Diagram V9

Diagram I2

Delta Grd B Ph 2 CT

3

-

Diagram I3

Delta Grd B Ph 3 CT

3-phase, 4-wire high-
leg

(2)

(wildcat)

≤690 V

3

-

Diagram V10

Diagram I3

Delta High Leg

For demo use

-

-

-

-

-

Demo

(1) For true single-phase circuits, connect only V1 to N and wire the CT to I1. Use only the Phase 1 results.

(2) Delta Grounded B Phase and Delta High-Leg are not supported above 690 V L-L. Use the 3-phase, 3-wire Delta circuit type.

(3) 2 PTs used in open-delta configuration.