Data log single record retrieval – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 121

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

121

Logging

Chapter 6

Data Log Single Record Retrieval

A controller or application can sequentially retrieve records from the Data Log
files by following the process described in this section, following these general
tasks.

1.

Read the number of log files from the

Statistics.Logging

table.

2.

Write the

Configuration.Log_Read

table and read the filename from the

LoggingResults.DataLog_FileName

table until the desired log file is

selected.

3.

Write the selected file name into the

Configuration.DataLogFile

table.

4.

Perform sequential reads of the

LoggingResults.Data_Log

table and store

the results in a suitable location.

The

Statistics.Logging

file contains the following Data Log information:

Element 7 and 8, the number of Data Log records

Element 9, the number of Data Log files

The

Configuration.Log_Read

table contains the following elements:

Element 0. Write a value of 7 to request the next Data Log file name

Element 1: Write a 0 to return the most recent file name first or a 1 to
return the oldest file name first

The

LoggingResults.DataLog_FileName

table returns a string containing the

requested file name. The file name contains the starting date and time of the log
file, as described in

File Names on page 119

25

DataLog_Parameter_21

Values of user-selected or default
parameters

26

DataLog_Parameter_22

27

DataLog_Parameter_23

28

DataLog_Parameter_24

29

DataLog_Parameter_25

30

DataLog_Parameter_26

31

DataLog_Parameter_27

32

DataLog_Parameter_28

33

DataLog_Parameter_29

34

DataLog_Parameter_30

35

DataLog_Parameter_31

36

DataLog_Parameter_32

Table 20 - Data Log Logged Parameters

Element

Tag Name

Description

Advertising