Alarm Log

The alarm log records information when an alarm occurs. The alarm log is up
to 100 records deep. The alarm log cannot be cleared.

Alarm Log Results

Alarm log records can be retrieved from the PowerMonitor 5000 web page or ftp
server. Alarm log records can also be retrieved sequentially by using the data table
interface.

File Name

The alarm log is named Alarm_Log.csv.

Logged Parameters

The alarm log operates in a circular, or FIFO fashion. The first is a header naming
the logged parameters. Each subsequent record is a structure of INT16 elements
containing the following parameters.

Table 26 - Alarm Log Logged Parameters

Tag Name

Description

Alarm_Record_Identifier

Used to verify record sequence when returning multiple
records.

Alarm_Timestamp_Year

The year when the record was recorded.

Alarm_Timestamp_Mth_Day

The month and day when the record was recorded.

Alarm_Timestamp_Hr_Min

The hour and minute when the record was recorded.

Alarm_Timestamp_Sec_ms

The seconds and milliseconds when the record was
recorded.

Alarm Type

Indicates the type of event that has occurred.

Alarm Code

Indicates information about the alarm.