Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 314

Advertising
background image

314

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

19

Int16

MeanPathDelayToMaster_A

MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 0 to bit 15)

0…0xffff

20

Int16

MeanPathDelayToMaster_B

MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 16 to bit 31)

0…0xffff

21

Int16

MeanPathDelayToMaster_C

MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 32 to bit 47)

0…0xffff

22

Int16

MeanPathDelayToMaster_D

MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 48 to bit 63)

0…0xffff

23

Int16

MasterClockIdentity_AB

MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Master Clock.

0…0xffff

24

Int16

MasterClockIdentity_CD

MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Master Clock.

0…0xffff

25

Int16

MasterClockIdentity_EF

MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Master Clock.

0…0xffff

26

Int16

LocalClockIdentity_AB

MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Local Clock.

0…0xffff

27

Int16

LocalClockIdentity_CD

MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Local Clock.

0…0xffff

28

Int16

LocalClockIdentity_EF

MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Local Clock.

0…0xffff

29

Int16

LocalClockClass

An attribute defining a clock's TAI traceability

0…255

30

Int16

LocalTimeAccuracy

An attribute defining the accuracy of a clock

0…255

31

Int16

LocalOffsetScaledLogVariance

An attribute defining the stability of a clock

0…0xffff

32

Int16

NumberOfPorts

NumberOfPorts specifies the number of PTP ports on the device.

1

33

Int16

PortState

PortStateInfo specifies the current state of each PTP port on the device

1…9

34

Int16

DomainNumber

DomainNumber specifies the PTP clock domain.

0…255

35

Int16

ClockType

The value of ClockType shall indicate the type of PTP node as defined in Table 5-47.13 in CIP
sepecification Volume 1.

0…0xffff

36

Int16

Steps removed

StepsRemoved specifies the number of communication paths traversed between the local clock and
the grandmaster clock.

0…0xffff

37…48

Int16

Reserved

For future use

Table 122 - Status.IEEE1588 Data Table (M6 model)

Element
Number

Type

Tag Name

Description

Range