Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 298

Advertising
background image

298

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

5

Real

Range1_Current_Input_Inverted

Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

-1…123

6

Real

Range1_Voltage_Rotation

Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range

-1…132

7

Real

Range1_Current_Rotation

Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range

-1…321

8

Real

Range2_L85_C98_Status

This is the pass fail status for Range 1 diagnostics.
0 = Pass
1 = Failed

0 or 1

9

Real

Range2_Voltage_Input_Inverted

Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

-1…123

10

Real

Range2_Current_Input_Inverted

Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

-1…123

11

Real

Range2_Voltage_Rotation

Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range

-1…132

Table 110 - Status.Wiring_Diagnostics Data Table

Element
Number

Type

Tag Name

Description

Range

Advertising