Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 299

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

299

PowerMonitor 5000 Unit Data Tables

Appendix A

12

Real

Range2_Current_Rotation

Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range

-1…321

13

Real

Range3_L52_L95_Status

This is the pass fail status for Range 1 diagnostics.
0 = Pass
1 = Failed

0 or 1

14

Real

Range3_Voltage_Input_Inverted

Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

-1…123

15

Real

Range3_Current_Input_Inverted

Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

-1…123

16

Real

Range3_Voltage_Rotation

Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range

-1…132

17

Real

Range3_Current_Rotation

Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range

-1…321

18

Real

Voltage_Phase_1_Angle

Shows the present phase angle of this channel. Always 0 degrees for voltage phase 1.

0…359.99

19

Real

Voltage_Phase_1_Magnitude

Shows the present magnitude of this phase.

0…9,999,999

20

Real

Voltage_Phase_2_Angle

Shows the present phase angle of this channel.

0…359.99

21

Real

Voltage_Phase_2_Magnitude

Shows the present magnitude of this phase.

0 …9,999,999

22

Real

Voltage_Phase_3_Angle

Shows the present phase angle of this channel.

0…359.99

23

Real

Voltage_Phase_3_Magnitude

Shows the present magnitude of this phase.

0…9,999,999

24

Real

Current_Phase_1_Angle

Shows the present phase angle of this channel.

0…359.99

25

Real

Current_Phase_1_Magnitude

Shows the present magnitude of this phase.

0…9,999,999

26

Real

Current_Phase_2_Angle

Shows the present phase angle of this channel.

0…359.99

Table 110 - Status.Wiring_Diagnostics Data Table

Element
Number

Type

Tag Name

Description

Range

Advertising