Applications, Setup, Command – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 58

Advertising
background image

58

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Chapter 4

Metering

Applications

This applies to all models.

Setup

Only basic metering setup is required.

Command

The

Command.Wiring_Corrections

table comprises the following parameters.

Wiring_Correction_Commands

Wiring_Correction_Commands determines the type of wiring correction to be
performed when the command executes. These are the selections:

0 = No command
1 = Correct wiring automatically by using Power Factor Range 1 results
2 = Correct wiring automatically by using Power Factor Range 2 results
3 = Correct wiring automatically by using Power Factor Range 3 results
4 = Correct wiring by using manual input mapping parameters
5 = Remove all wiring corrections.

Input_V1_Mapping
Input_V2_Mapping
Input_V3_Mapping
Input_I1_Mapping
Input_I2_Mapping
Input_I3_Mapping

This collection of parameters determines the mapping of physical voltage inputs
to logical voltage channels and physical current inputs to logical current channels.
The following are the permitted values:

1 = Map the physical input to logical channel 1
2 = Map the physical input to logical channel 2
3 = Map the physical input to logical channel 3
-1 = Map the physical input to logical channel 1 and invert its polarity
-2 = Map the physical input to logical channel 2 and invert its polarity
-3 = Map the physical input to logical channel 3 and invert its polarity

The values of these parameters are ignored if automatic wiring correction is
selected in the command. If manual input mapping is selected, all mapping
parameters are required and the combination is checked for validity (mapping of
two physical inputs to the same metering channel is not permitted).