Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 283

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

283

PowerMonitor 5000 Unit Data Tables

Appendix A

23

Real

IEEE1159_Voltage_Imbalance_Limit_%

The percent of voltage Imbalance to create an imbalance event

3

1.00…10.00

24

Real

IEEE1159_Current_Imbalance_Limit_%

The percent of current Imbalance to create an imbalance event

25

1.00…50.00

25

Real

IEEE1159_DCOffset_Harmonic_Avg_Intvl_m

The a rolling average interval for DC offset and Harmonics in
minutes

5

1…15

26

Real

IEEE1159_Voltage_DCOffset_Limit_%

The percent of DC offset limitation

0.1

0.00…1.00

27

Real

IEEE1159_Voltage_THD_Limit_%

The percent of voltage THD limitation

5

0.00…20.00

28

Real

IEEE1159_Current_THD_Limit_%

The percent of current THD limitation

10

0.00…20.00

29

Real

IEEE1159_PowerFrequency_Avg_Intvl_s

The rolling average interval for power frequency in seconds.

1

1…10

30

Real

IEEE1159_PowerFrequency_Limit_Hz

The limitation on power frequency variation in Hz.

0.1

0.1…0.2

31

Real

IEEE1159_PowerFrequency_Hysteresis_Hz

Hysteresis of power frequency

0.02

0.01…0.05

32

Real

IEEE519_Compliance_Parameter

IEEE 519 Compliance Parameter
0 = Current
1= Voltage

0

0…1

33

Real

IEEE519_MAX_Isc_Amps

Short circuit current available at the point of common coupling.
(PCC) IMPORTANT: When Isc is ‘0’ or IL is ‘0’, the first row in IEEE 519
Current Distortion Limits table is selected for compliance.

0

0.00…1,000,000.0
0

34

Real

IEEE 519 MAX_IL_Amps

Average maximum demand for current for the preceding 12
months. IMPORTANT: When IL is ‘0’ the current THD instead of TDD is
used for compliance.

0

0.00…1,000,000.0
0

35 … 49

Real

Reserved

Reserved for future use.

0

0

Table 78 - Configuration.PowerQuality Data Table

Element
Number

Type

Tag Name

Description

Default

Range