Data log, Setup – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 113

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

113

Logging

Chapter 6

Data Log

The data log stores user-selected values at a time interval defined in parameter
Data_Logging_Interval. The power monitor can store up to 60,000 records of up
to 32 parameters. The default logging interval is 15 minutes.

Setup

The Data Log requires the following to be configured:

Basic metering setup

Date and Time setup

The first 22 parameters in the Data Log are configured by default, as listed in the
Logged Parameters table. Further configuration of the Data Log is not required if
the default selections satisfy your data logging needs.

To customize your Data Log, change the following set-up parameters, which
define the behavior of the Data Log. These parameters are found in the

Configuration.Data_Log

table.

Data_Logging_Interval

Data_Logging_Interval defines the logging interval in seconds. These are the
selections:

0 = Disables data logging
-1 = synchronize log with demand period
1…3600 = User-selected data logging interval. Default is 900 (15 minutes)

Logging Mode

Logging Mode selects how records are saved.

0 = Fill and stop recording when log is full.

1 = Overwrite when log is full starting with the earliest record.

DataLog_Parameter_1
DataLog_Parameter_2

DataLog_Parameter_32

These parameters define the set of records that are maintained in the data log.
The Configuration.Data_Log web page includes the descriptions of the default
selections for each parameter, even if the selections have been changed from their
default value.

Advertising