Optional devicenet network communication – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 38

Advertising
background image

38

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Chapter 2

Install the PowerMonitor 5000 Unit

Optional DeviceNet Network Communication

An optional DeviceNet port can be factory-installed in PowerMonitor 5000
units with a catalog number ending in -DNT, and can also be purchased from
Rockwell Automation and installed by the user.

For information on installing the optional communication card, see the
PowerMonitor 5000 Optional Communication Modules Installation
Instructions, publication

1426-IN002

.

For detailed DeviceNet system installation information, including cable lengths,
the placement of terminating resistors, power supplies, and other media
components, refer to the DeviceNet Cable System Planning and Installation
Manual, publication

DNET-UM072

.

Install suitable terminating resistors at the ends of the DeviceNet cable.

Configuration options for optional DeviceNet communication include the node
address (MAC ID) and data rate. Defaults are node 63 and 125 Kbps.

ATTENTION: Power must be removed from the power monitor before inserting
or removing an optional communication card. Inserting or removing an
optional communication card under power can damage the card or the power
monitor.

IMPORTANT

You must install and wire a suitable 24V DC power supply to the V+ and V-
conductors in the DeviceNet cable. The power monitor consumes less than
50 mA from the DeviceNet 24V DC supply.

Table 7 - DeviceNet Terminal Block Wiring Connections

Terminal

Signal

Function

Color

1

COM (V-)

Common

Black

2

CAN_L

Signal Low

Blue

3

SHIELD

Shield

Uninsulated

4

CAN_H

Signal High

White

5

VDC+ (V+)

Power Supply

Red