PowerMonitor 5000 Unit Data Tables

Appendix A

Status.OptionalComm

Table 117 - Table Properties

CIP Instance Number

835

PCCC File Number

N44

No. of Elements

30

Length in Words

30

Data Type

Int16

Data Access

Read Only

Table 118 - Status.OptionalComm Data Table

Element
Number

Type

Tag Name

Description

Units

Range

0

Int16

Network_Type

0x25 = DeviceNet
0x65 = ControlNet

-

0 …255

1

Int16

Firmware_Version

Optional communication firmware version

Network_
Type
dependent

0…255

2

Int16

Firmware_Build

Optional communication firmware build

Network_
Type
dependent

0

3

Int16

Serial_Number_Low

Low 16-bit serial number

-

0

4

Int16

Serial_Number_High

High 16-bit serial number

-

0

5

Int16

Optional_Port_Status

Bit15: Watchdog Timeout indicator

0: The application and ABCC communicate normally
1: The application lost the communication with ABCC module, so the watch dog times-out.

Bit14 to Bit5 reserved for future use.
Bit4: SUP bit

0: Module is not supervised;
1: Module is supervised.

Bit3 … Bit 0: Current status of Anybus module

000: SETUP
001: NW_INIT
010: WAIT_PROCESS
011: IDLE
100: PROCESS_ACTIVE
101: ERROR
110: reserved
111: EXCEPTION

-

0…7

6

Int16

Exception_Code

Last exception
0 = No exception
1 = Application timeout
2 = Invalid device address
3 = Invalid communication setting
4 = Major unrecoverable app event
5 = wait for reset
6 = Invalid process data config
7 = Invalid application response
8 = Non-volatile memory checksum error
Other value = reserved

-

0…8