Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 256

Advertising
background image

256

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

32

Real

Parameter
Selection 5

Selection of the input parameter from the

Setpoint Parameter Selection List

.

0

0…105

33

Real

Input Reference
Selection 5

Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value

0

0

34

Real

Test Condition 5

0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals

0

0…3

35

Real

Evaluation Type 5

0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)

0

0…3

36

Real

Threshold 5

The value, percent, or state that triggers the output action.

0

-10,000,000…
10,000,000

37

Real

Hysteresis 5

The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).

0

0…10,000,000

38

Real

Assert Delay
Seconds 5

The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.

0

0.000…3600

39

Real

Deassert Delay
Seconds 5

The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.

0

0.000…3600

40…49

Real

Reserved

Future Use

0

0

Table 62 - Configuration.Setpoints_1_5 Data Table

Element
Number

Type

Tag Name

Description

Default

Range