Status.wiring_diagnostics – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 297

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

297

PowerMonitor 5000 Unit Data Tables

Appendix A

Status.Wiring_Diagnostics

Table 109 - Table Properties

CIP Instance Number

829

PCCC File Number

F38

No. of Elements

33

Length in Words

66

Data Type

Real

Data Access

Read Only

Table 110 - Status.Wiring_Diagnostics Data Table

Element
Number

Type

Tag Name

Description

Range

0

Real

Command_Status

This is the wiring diagnostics command status.
0 = Command Active
1 = Input Level Low
2 = Disabled
3 = Waiting Command

0…3

1

Real

Voltage_Input_Missing

Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing

-1…123

2

Real

Current_Input_Missing

Reports on all three phase.
-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing

-1…123

3

Real

Range1_L97_C89_Status

This is the pass fail status for Range 1 diagnostics.
0 = Pass
1 = Failed

0 or 1

4

Real

Range1_Voltage_Input_Inverted

Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted

-1…123

Advertising