Configuration.Metering.Basic

Table 53 - Table Properties

CIP Instance Number

802

PCCC File Number

F11

No. of Elements

33

Length in Words

66

Data Type

Real

Data Access

Read/Write

Table 54 - Configuration.Metering.Basic Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Real

Metering_Mode

Configures the input wiring for metering.
0 = Demo
1 = Split-phase
2 = Wye
3 = Delta 2 CT
4 = Delta 3 CT
5 = Open Delta 2 CT
6 = Open Delta 3 CT
7 = Delta Gnd B Ph 2 CT
8 = Delta Gnd B Ph 3 CT
9 = Delta High Leg

2

0…9

1

Real

V1_V2_V3_PT_Primary

The primary voltage value of the PT transformer.

480

0…1,000,000

2

Real

V1_V2_V3_PT_Secondary

The secondary voltage value of the PT transformer.

480

0…690

3

Real

I1_I2_I3_CT_Primary

The primary ampere value of the CT transformer.

5

0…1,000,000

4

Real

I1_I2_I3_CT_Secondary

The secondary ampere value of the CT transformer.

5

5

5

Real

VN_PT_Primary

The primary voltage value of the PT transformer.

480

0…1,000,000

6

Real

VN_PT_Secondary

The secondary voltage value of the PT transformer.

480

0…690

7

Real

I4_CT_Primary

The primary ampere value of the CT transformer.

5

0…1,000,000

8

Real

I4_CT_Secondary

The secondary ampere value of the CT transformer.

5

5

9

Real

Nominal_System_LL_Voltage

Nominal line to line voltage value or line to line voltage rating of the system being
metered.

480

0…1,000,000

10

Real

Nominal_System_Frequency

Nominal frequency of the system.

60

50 …60

11

Real

Realtime_Update_Rate

Selects the update rate for the realtime table and the setpoint calculations.
0 = Single cycle averaged over 8 cycles
1 = Single cycle averaged over 4 cycles
2 = 1 cycle with no averaging
3 = 200ms per EN61000-4-30 (M6 model only)

0

0…2

12

Real

Demand_Source

When item ‘Demand Broadcast Master Select’ of the Ethernet table is set to master a
selection of 0…2 and 4 sets the type of master input. In this case item 3 is ignored.
When the ‘Demand Broadcast Master Select’ of the Ethernet table is set to slave then
any of these inputs can set the end of the demand period.
0=Internal Timer
1=Status Input 2
2=Controller Command
3=Ethernet Demand Broadcast

0

0…3