Status.wiring_corrections – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 311

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

311

PowerMonitor 5000 Unit Data Tables

Appendix A

Status.Wiring_Corrections

Table 119 - Table Properties

CIP Instance Number

834

PCCC File Number

N43

No. of Elements

14

Length in Words

14

Data Type

Int16

Data Access

Read Only

Table 120 - Status.Wiring_Corrections Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Int16

Wiring_Correction_Commands

0 = No command
1 = Correct wiring by using Range 1 results, Lagging 97 PF to Leading 89 PF
2 = Correct wiring by using Range 2 results, Lagging 85 PF to leading 98 PF
3 = Correct wiring by using Range 3 results, Lagging 52 PF to lagging 95 PF
4 = Correct wiring by using manual input parameters
5 = Remove all wiring corrections

0

0…5

1

Int16

Input_V1_Mapping

This parameter logically maps a physical voltage channel to V1.
1 = V1
2 = V2
3 = V3
-1 = V1 inverted
-2 = V2 inverted
-3 = V3 inverted

1

-3…-1
1…3

2

Int16

Input_V2_Mapping

This parameter logically maps a physical voltage channel to V2.
1 = V1
2 = V2
3 = V3
-1 = V1 inverted
-2 = V2 inverted
-3 = V3 inverted

2

-3… -1
1…3

3

Int16

Input_V3_Mapping

This parameter logically maps a physical voltage channel to V3.
1 = V1
2 = V2
3 = V3
-1 = V1 inverted
-2 = V2 inverted
-3 = V3 inverted

3

-3…-1
1 …3

4

Int16

Input_I1_Mapping

This parameter logically maps a physical current channel to I1.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted

1

-3…-1
1…3