Data log results files, File names – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 119

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

119

Logging

Chapter 6

Data Log Results Files

The PowerMonitor 5000 unit stores the data log in multiple comma-separated-
value (.csv) files, and selects a file duration based on the value of the
Data_Logging_Interval parameter.

In addition, the active data log file is closed and a new file is created when any of
the following events occur:

Initial powerup of the power monitor

Subsequent powerup, if the active data log file is older than the expected
duration

If the Data_Logging_Interval or any other data log parameter is changed

The Data_Log_Mode parameter determines what happens when the log contains
60,000 records:

If set to 0 = Fill and stop recording when log is full, no new data log files
are created and no more data is logged.

If set to 1 = Overwrite when log is full starting with the earliest record, a
new file is created and data logging continues uninterrupted. This is the
default setting.

File Names

Data log file names have the following semantics:

DataLog_YYYYMMDD_hhmm_HH.csv, where:

YYYYMMDD_hhmm - the file creation date and time

HH - UTC hour avoids duplication during daylight-saving time transition

Interval, Seconds

Log File Duration

File End Date

Maximum Records

1~30

Hour

New hour, xx:00:00
(hh:mm:ss)

3600

31~90

Day

New day, 00:00:00
(hh:mm:ss)

2788

>90

Week

Sunday of a week, 00:00:00
(hh:mm:ss)

6646

Advertising