Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

237

PowerMonitor 5000 Unit Data Tables

Appendix A

144

1

SINT

KYZCommFaultMode

The Default output state on communication loss defines the behavior
of the output if the power monitor experiences a loss of
communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local Control

N/A

0…4

1

SINT

Pad30

For alignment purpose

2

INT

Pad31

For alignment purpose

148

1

SINT

R1CommFaultMode

The Default output state on communication loss defines the behavior
of the output if the power monitor experiences a loss of
communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local Control

N/A

0…4

1

SINT

Pad32

For alignment purpose

2

INT

Pad33

For alignment purpose

152

1

SINT

R2CommFaultMode

The Default output state on communication loss defines the behavior
of the output if the power monitor experiences a loss of
communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local Control

N/A

0…4

1

SINT

Pad34

For alignment purpose

2

INT

Pad35

For alignment purpose

156

1

SINT

R3CommFaultMode

The Default output state on communication loss defines the behavior
of the output if the power monitor experiences a loss of
communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local Control

N/A

0…4

1

SINT

Pad36

For alignment purpose

2

INT

Pad37

For alignment purpose

Table 44 - Configuration.Instance Data Table

Start
Byte

Size Type

Tag

Name

Description

Units

Range