Powerquality.ieee1159_results (m6 model) – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 357

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

357

PowerMonitor 5000 Unit Data Tables

Appendix A

PowerQuality.IEEE1159_Results (M6 model)

Table 181 - Table Properties

CIP Instance Number

863

PCCC File Number

F72

No. of Elements

26

Length in Words

52

Data Type

Real

Data Access

Read Only

Table 182 - PowerQuality.IEEE1159_Results Data Table

Element
Number

Type

Tag Name

Description

Units

Range

0

Real

Metering_Date_Stamp

Date of cycle collection MMDDYY

MMDDYY

0…123199

1

Real

Metering_Time_Stamp

Time of cycle collection hhmmss

hhmmss

0…235959

2

Real

Metering Microsecond Stamp

Microsecond of cycle collection

uS

0.000…999999

3

Real

IEEE1159_Volts_Imbalance_%

The rolling average for IEEE1159 voltage imbalance

%

0.0…100.00

4

Real

IEEE1159_Current_Imbalance_%

The rolling average for IEEE1159 current imbalance

%

0.0…100.00

5

Real

IEEE1159_Power_Frequency_Hz

The rolling variation from nominal frequency setting.

Hz

0.0…70.00

6

Real

IEEE1159_V1_DC_Offset_%

The rolling average for V1 voltage dc offset

%

0.0…100.00

7

Real

IEEE1159_V2_DC_Offset_%

The rolling average for V2 voltage dc offset

%

0.0…100.00

8

Real

IEEE1159_V3_DC_Offset_%

The rolling average for V3 voltage dc offset

%

0.0…100.00

9

Real

IEEE1159_V1_THD_%

The rolling average for V1 Voltage THD

%

0.0…100.00

10

Real

IEEE1159_V2_THD_%

The rolling average for V2 Voltage THD

%

0.0…100.00

11

Real

IEEE1159_V3_THD_%

The rolling average for V3 Voltage THD

%

0.0…100.00

12

Real

IEEE1159_I1_THD_%

The rolling average for I1 Current THD

%

0.0…100.00

13

Real

IEEE1159_I2_THD_%

The rolling average for I2 Current THD

%

0.0…100.00

14

Real

IEEE1159_I3_THD_%

The rolling average for I3 Current THD

%

0.0…100.00

15…25

Real

Reserved

Reserved

0.0

Advertising