Logic Functions

Chapter 7

Relative_Setpoint_Interval_m

This tag, found in the

Configuration.PowerQuality

table, defines the length of

the sliding average interval used in all setpoints with Percent of Sliding Reference
evaluation type. Range: 1 (default)…1440 minutes

Setpoint Logic Gate Setup

The tags listed below can be used to configure setpoint logic gates and are found
in the

Configuration.Setpoint_Logic Data Table

.

Logic Level 1 Gate n Function

Selects the logic type for the gate. These are the choices:

0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR

L1_Gn Input 1
L1_Gn Input 2
L1_Gn Input 3
L1_Gn Input 4

Selects input parameters for the nth logic gate (n = 1 … 10). Each AND, NAND,
OR, and NOR gate has up to four inputs. These are the choices:

0 = Disabled
1 = Setpoint 1; -1 = Setpoint 1 inverted
2 = Setpoint 2; -2 = Setpoint 2 inverted
3 = Setpoint 3; -3 = Setpoint 3 inverted

20 = Setpoint 20; -20 = Setpoint 20 inverted

Setpoint Output Setup

The tags listed below can be used to optionally tie output actions to setpoints,
and are found in the

Configuration.Setpoint_Outputs

table.

IMPORTANT

XOR and XNOR use Inputs 1 and 2; both must be configured at the same time,
otherwise an error is reported and the logic gate configuration is rejected.