Configuration.powerquality – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 282

Advertising
background image

282

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

Configuration.PowerQuality

Table 77 - Table Properties

CIP Instance Number

815

PCCC File Number

F24

No. of Elements

50

Length in Words

100

Data Type

Real

Data Access

Read/Write

Table 78 - Configuration.PowerQuality Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Real

Sag1_Trip_Point_%

The percent of Nominal System Voltage that creates a level 1 sag
condition.

90

0.00…100.00

1

Real

Sag1_Hysteresis_%

The percent of hysteresis for sag 1 condition.

2

0.00…10.00

2

Real

Sag2_Trip_Point_%

The percent of Nominal System Voltage that creates a level 2 sag
condition.

80

0.00…100.00

3

Real

Sag2_Hysteresis_%

The percent of hysteresis for sag 2 condition.

2

0.00…10.00

4

Real

Sag3_Trip_Point_%

The percent of Nominal System Voltage that creates a level 3 sag
condition.

70

0.00…100.00

5

Real

Sag3_Hysteresis_%

The percent of hysteresis for sag 3 condition.

2

0.00…10.00

6

Real

Sag4_Trip_Point_%

The percent of Nominal System Voltage that creates a level 4 sag
condition.

40

0.00…100.00

7

Real

Sag4_Hysteresis_%

The percent of hysteresis for sag 4 condition.

2

0.00…10.00

8

Real

Sag5_Trip_Point_%

The percent of Nominal System Voltage that creates a level 5 sag
condition.

5

0.00…100.00

9

Real

Sag5_Hysteresis_%

The percent of hysteresis for sag 5 condition.

2

0.00…10.00

10

Real

Swell1_Trip_Point_%

The percent of Nominal System Voltage that creates a level 1 swell
condition.

110

100.00…200.00

11

Real

Swell1_Hysteresis_%

The percent of hysteresis for swell 1 condition.

2

0.00…10.00

12

Real

Swell2_Trip_Point_%

The percent of Nominal System Voltage that creates a level 2 swell
condition.

120

100.00…200.00

13

Real

Swell2_Hysteresis_%

The percent of hysteresis for swell 2 condition.

2

0.00…10.00

14

Real

Swell3_Trip_Point_%

The percent of Nominal System Voltage that creates a level 3 swell
condition.

140

100.00…200.00

15

Real

Swell3_Hysteresis_%

The percent of hysteresis for swell 3 condition.

2

0.00…10.00

16

Real

Swell4_Trip_Point_%

The percent of Nominal System Voltage that creates a level 4 swell
condition.

180

100.00…200.00

17

Real

Swell4_Hysteresis_%

The percent of hysteresis for swell 4 condition.

2

0.00…10.00

18

Real

Capture_Pre_Event_Cycles

The pre-event cycles for waveform capture

5

5…10

19

Real

Capture_Post_Event_Cycles

The post-event cycles for waveform capture

15

2…30

20

Real

Relative_Setpoint_Intvl_m

The interval setting in minutes for the rolling average of all relative
setpoints.

60

1…1440

21

Real

IEEE1159_Parameter_Hysterisis_%

The percent of hysteresis for IEEE1159 output parameters.

2

0.00…10.00

22

Real

IEEE1159_Imbalance_Averaging_Intvl_m

The rolling average interval for Imbalance in minutes

15

15…60