Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 172

Advertising
background image

172

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Chapter 8

Other Functions

Once security is enabled and an Admin class account is set up during initial
configuration, the remaining security configuration can be done through the
network web page.

If you want to configure power monitors by using software, such as FactoryTalk
EnergyMetrix RT software, set up at least one Application class account.

This table summarizes the security classes, privileges, access, and limits that apply
to the PowerMonitor 5000 unit.

The following rules further define security operation:

The USB Admin account can be accessed only through the web page when
connected via USB.

Only one Admin can be active at a time, including the USB Admin class.

A logged in account remains active until logged out or until 30 minutes has
elapsed without writing a configuration parameter. FTP access to log files
remains until the account is logged out.

Only an Admin class account can add, remove, or edit accounts. An
Admin class account cannot delete itself and the default USB Admin
account cannot be deleted.

An Application class account is used for access by using CIP or PCCC
protocols via native Ethernet network or optional DeviceNet network
communication. An Application class account logs in by writing its
username to the

Security.Username

table and then its password to the

Security.Password

table within 30 seconds. An application can obtain

security status information by reading the

Status.TableWrite

data table.

Table 30 - Account Classes and Privileges

Account Class

Privileges

Interface

Maximum Number of Accounts

USB admin

Manage security accounts
Read data
Write configuration parameters
Download log files

USB only web page

1

Admin

Manage security accounts
Read data
Write configuration parameters
Download log files

USB and native Ethernet web page

10

User

Read data
Download log files

USB and native Ethernet web page

20

Application

Read data
Write configuration parameters
Download log files

Native EtherNet/IP and optional DeviceNet
communication CIP assembly and
parameters objects CSP/PCCC data tables

10

privileges with security disabled (all)

Read data
Write configuration parameters
Download log files

Any

-

security enabled but no user logged in

Read data

Any

-