324

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

Command.System_Registers

Table 129 - Table Properties

CIP Instance Number

838

PCCC File Number

F47

No. of Elements

45

Length in Words

90

Data Type

Real

Data Access

Write Only

Table 130 - Command.System_Registers Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Real

Command Word 1

These commands can be sent to the power monitor. When using the optional elements the
command table must be sent complete with all elements present. If the single password table
is used to gain access to configuration items then the command can be sent alone without
optional settings. The command options are:
0 = No Action

1=Set kWh Register

2=Set kVARh Register

3=Set kVAh Register

4= Set kAh Register

5= Clear All Energy Registers

6=Set Status 1 Count

7=Set Status 2 Count

8=Set Status 3 Count

9=Set Status 4 Count

10=Force KYZ Output On

11=Force KYZ Output Off

12=Remove Force from KYZ

13=Force Relay 1 Output On

14=Force Relay 1 Output Off

15=Remove Force from Relay 1

16=Force Relay 2 Output On

17=Force Relay 2 Output Off

18=Remove Force from Relay 2

19=Force Relay 3 Output On

20=Force Relay 3 Output Off

21=Remove Force from Relay 3

22=Restore Factory Defaults

23=Reset Power Monitor System.

Important: If a command is received that is not supported by your catalog number the
command is ignored.

0

0…23

1

Real

Command Word 2

0 = No Action

1=Clear Min/Max Records

2=Store and clear current Load Factor Record

3=Clear Load Factor Log

4=Store and clear current TOU Record

5=Clear TOU Log

6= Clear Setpoint Log

7= Setpoint accumulators

8= Clear Error Log

9= Clear Energy Log

10=Clear Data Log

11=Perform Wiring Diagnostics

12=Log Off

13=Clear Trigger Data Log

14 = Trigger Waveform

15 = Clear Waveform

16 = Metering Data Snapshot

17 = Clear Power Quality Log

18 = Clear Setpoint Logic Gate Accumulators

19 = Reserved for future use.

Important: If a command is received that is not supported by your catalog number the
command is ignored.

0

0…18

2

Real

Clear Single Min/Max
Records

When invoking the Min/Max Clear command, this value can be sent to specify a single
parameter. If clearing all values this is not required.
0 = Clear All Parameters
1= Clear the 1st Min/Max Record
2= Clear the 2nd Min/Max Record . . . To the end of the Min/Max Parameters

0

0…82

3

Real

Clear Single Setpoint or
Logic Gate Accumulator

When invoking the Setpoint or Setpoint Logic Gate Accumulator Clear command this value
can be sent to specify a single parameter. If clearing all values this is not required.
0 = Clear All Accumulators
1= Clear the 1st time accumulator
2= Clear the 2nd time accumulator…
20= Clear the 20th time accumulator

0

0…10 (M5);
0…10,
logic gate
accumulator,
0…20 setpoints
(M6)