Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

359

PowerMonitor 5000 Unit Data Tables

Appendix A

PowerQuality.IEEE519_ Results (M6 model)

The PowerMonitor 5000 M6 model returns short- and long-term rolling average
harmonic distortion data for the fundamental and the first 40 harmonic
frequencies. These results are presented in six similar data tables.

These tables share the following properties.

The IEEE519 Results data tables share a common structure. In the data table
template shown, substitute the following into the Data Table Name and Tag
Name strings to obtain the specific names:

For ‘<CH>’, substitute ‘CH1’, ‘CH2’, or ‘CH3’.

For ‘<Term>’, substitute ‘ShortTerm’ or ‘LongTerm’.

For example, the tag CH3_5th_Harmonic_IEEE519_ShortTerm in the
PowerQuality.IEEE519_CH3 _ShortTerm_Results table returns the short-term
5th harmonic value for Channel 3.

Table 185 - Table Properties

Data Table Name

CIP Instance
Number

PCCC File No.

PowerQuality.IEEE519_CH1_ShortTerm_Results

895

F104

PowerQuality.IEEE519_CH2_ShortTerm_Results

896

F105

PowerQuality.IEEE519_CH3_ShortTerm_Results

897

F106

PowerQuality.IEEE519_CH1_LongTerm_Results

898

F107

PowerQuality.IEEE519_CH2_LongTerm_Results

899

F108

PowerQuality.IEEE519_CH3_LongTerm_Results

900

F109

No. of Elements

44

Length in Words

88

Data Type

Real

Data Access

Read Only

IMPORTANT

Channel assignments are based on the value of the tag
IEEE519_Compliance_Parameter found in the Configuration.Power_Quality
table.

IEEE519_Compliance_Parameter

Channel 1

Channel 2

Channel 3

0 = Current

I1

I2

I3

1 = Voltage (Wye and Split Phase)

V1-N

V2-N

V3-N

1 = Voltage (Delta)

V1-V2

V2-V3

V3-V1