Install the PowerMonitor 5000 Unit

Figure 11 - Diagram V9 - 3-phase, 3-wire Grounded B-phase (690V AC line-to-line maximum)

(1) You can also connect V2 to L2. In this case, omit the connection from V2 to VN.

Figure 12 - Diagram V10 - 3-phase, 4-wire High-leg Delta (690V AC line-to-line maximum)

Metering_Mode = Delta Grd B Ph 2 CT
or Delta Grd B Ph 3 CT, as applicable

V1

V2

VG

V3

VN

PowerMonitor 5000

Fuses (by user)

L1

L2

L3

Line

Ground

Distribution

Ground

Load

(1)

Metering_Mode = Delta High-leg

V1

V2

VG

V3

VN

PowerMonitor 5000

Fuses (by user)

High-leg

Transformer

(by user)

L1

L2

L3

N

N

C

B

A

Ground

Load