Status.general – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 291

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

291

PowerMonitor 5000 Unit Data Tables

Appendix A

Status.General

Table 101 - Table Properties

CIP Instance Number

823

PCCC File Number

N32

No. of Elements

55

Length in Words

55

Data Type

Int16

Data Access

Read Only

Table 102 - Status.General Data Table

Element
Number

Type

Tag Name

Description

Range

0

Int16

Bulletin_Number

1426

0 or 1426

1

Int16

Device_Class

Describes the product device type.
5 = PM_PowerMonitor 5000

5

2

Int16

Model

Indicates the feature set included in the catalog number.
1 = M5
2 = M6

1 or 2

3

Int16

Communication_Options

Displays the communication hardware options.
0 = NAT (Native Ethernet)
1 = CNT (Optional ControlNet)
3 = DNT (Optional DeviceNet)

0, 1, 3

4

Int16

Nominal_Input_Current

5 = 5 Ampere

5

5

Int16

Metering_Class_Designation

Designation for the metering accuracy.
2 = Class Designation 0.2

2

6

Int16

Series_Letter

The current hardware revision. A…Z.

0…26

7

Int16

Manufacture_Month

Month the Unit was manufactured.

1…12

8

Int16

Manufacture_Day

Day the Unit was manufactured.

1…31

9

Int16

Manufacture_Year

Year the Unit was manufactured.

2010…2100

10

Int16

Overall_System_Status

Reports the overall system status of each system assembly.
0 = Status PASS
Bit 0 = 1: Assembly_Slot_0_inst_1_Error
Bit 1 = 1: Assembly_Slot_0_inst_2_Error
Bit 2 = 1: Assembly_Slot_1_inst_1_Error
Bit 3 = 1: Assembly_Slot_1_inst_2_Error
Bit 4 = 1: Assembly_Slot_2_inst_1_Error
Bit 5 = 1: Assembly_Slot_2_inst_2_Error
Bit 6 = 1: Assembly_Slot_3_inst_1_Error
Bit 7 = 1: Assembly_Slot_3_inst_2_Error
For the detailed error code, please refer to Status_RunTime Table.

0…65,535

11

Int16

Error_Log_Contents

Number of records in the Error Log.

0…65,535

12

Int16

Metering_Configuration_Locked

The hardware switch for configuration is locked.

0…1

13

Int16

PTP_Status

Indicates PTP status
0 = PTP Listening
1 = PTP Slave
2 = PTP Master

0…2

14…54

Int16

Reserved

Future Use.

0

Advertising