Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 330

Advertising
background image

330

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

29

Real

L3_kVA

L3 apparent power

kVA

0…9.999E15

30

Real

Total_kVA

Total apparent power

kVA

0…9.999E15

31

Real

L1_True_PF_%

L1 true power factor (full bandwidth)

%

0.00…100.00

32

Real

L2_True_PF_%

L2 true power factor (full bandwidth)

%

0.00…100.00

33

Real

L3_True_PF_%

L3 true power factor (full bandwidth)

%

0.00…100.00

34

Real

Avg_True_PF

Average true power factor

%

0.00…100.00

35

Real

L1_Disp_PF

L1 displacement power factor (fundamental only)

%

0.00…100.00

36

Real

L2_Disp_PF

L2 displacement power factor (fundamental only)

%

0.00…100.00

37

Real

L3_Disp_PF

L3 displacement power factor (fundamental only)

%

0.00…100.00

38

Real

Avg_Disp_PF

Average displacement power factor (fundamental only)

%

0.00…100.00

39

Real

L1_PF_Lead_Lag_Indicator

L1 lead or lag indicator for power factor
1 = leading
-1 = lagging

-1…1

40

Real

L2_PF_Lead_Lag_Indicator

L1 lead or lag indicator for power factor
1 = leading
-1 = lagging

-1…1

41

Real

L3_PF_Lead_Lag_Indicator

L1 lead or lag indicator for power factor
1 = leading
-1 = lagging

-1…1

42

Real

Total_PF_Lead_Lag_Indicator

L1 lead or lag indicator for power factor
1 = leading
-1 = lagging

-1…1

43

Real

Voltage Rotation

Voltage rotation has the following designations:
0 = Not metering
123 = ABC rotation
132 = ACB rotation
4 = No rotation

0…132

44

Real

Metering_Iteration

A number 0…9999999 that indicates that the metering
functions and internal communication are updating

0…9,999,999

45…55

Real

Resvd

Reserved

Table 136 - MeteringResults.RealTime_VIF_Power Data Table

Element
Number

Type

Tag Name

Description

Units

Range

Advertising