Power metering – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 67

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

67

Metering

Chapter 4

Power Metering

This function applies to all PowerMonitor 5000 models.

Only total three-phase power results are provided when Direct Delta or Open
Delta wiring modes are selected.

Table 10 - Power Metering Metered Parameters

Parameter

Description

Range

Units

L1_kW

Power of individual phase or sum of phases;
signed to show direction

-9.999E15…9.999E15

kW

L2_kW

L3_kW

Total_kW

L1_kVAR

Reactive power of individual phase or sum of
all phases; signed to show direction

-9.999E15…9.999E15

kVAR

L2_kVAR

L3_kVAR

Total_kVAR

L1_kVA

Apparent power of individual phase or sum of
all phases

0…9.999E15

kVA

L2_kVA

L3_kVA

Total_kVA

L1_True_PF_%

The ratio between power and apparent power
for individual phase or all phases

0.00…100.00

%

L2_True_PF_%

L3_True_PF_%

Avg_True_PF

L1_Disp_PF

The cosine of the phase angle between the
fundamental voltage and current for an
individual phase or all phases

0.00…100.00

%

L2_Disp_PF

L3_Disp_PF

Avg_Disp_PF

L1_PF_Lead_Lag_Indicator

Lead or lag indicator for power factor
1 = leading
-1 = lagging

-1…1

±

L2_PF_Lead_Lag_Indicator

L3_PF_Lead_Lag_Indicator

Total_PF_Lead_Lag_Indicator