Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

19

Install the PowerMonitor 5000 Unit

Chapter 2

3.

Use M4 or #8 screws to mount the power monitor to your panel with
1.16 N•m (10 lb•in) of torque.

4.

Ground the power monitor on a ground bus with a low-impedance earth
ground connection.

5.

Connect the ground bus to a functional earth ground on the panel.

Wire the PowerMonitor 5000
Unit

The PowerMonitor 5000 unit is equipped with screw terminals with pressure
plates and finger protection for the control power, I/O wiring, and voltage
connections. The I/O wiring block is removable.

Current sensing conductors are routed through openings in the power monitor
housing.

Figure 2 - Terminal Block Layout

Wire Requirements

IMPORTANT

The upper mounting slots are equipped with protective conductor terminals,
that must make metal-to-metal contact with the grounded mounting panel.

L1

L2

GND

24V

com

V1

V2

V3

VN

VG

---- S1
S2
---- S3
S4
---- S com
S com
---- K
Y
---- Z
R1 O
---- R1 com
R1 C
---- R2 O
R2 com
---- R2 C
R3 O
---- R3 com
R3 C

Wiring Category

Wire Type

Wire Size Range

Wires per Terminal

Recommended Torque

Control Power

Cu - 75 °C (167 °F)

0.25…2.5 mm

2

(22…14 AWG)

2 max

1.27 N•m (11.24 lb•in)

Input/Output (I/O)

0.5…0.8 mm

2

(20…18 AWG)

0.68 N•m (6 lb•in)

Voltage Sensing

0.75…2.5 mm

2

(18…14 AWG)

1.50 N•m (13.3 lb•in)

Current Sensing

4 mm

2

max (12 AWG max)

1 max

N/A