Waveform log (m6 model), Waveform data table retrieval – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 105

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

105

Logging

Chapter 6

Min/Max Record to be Returned

These are the choices:

0 = Use sequential return in the order selected
1…82 = Retrieve the selected record. See the Min_Max_Parameter table
for the list

Load Factor or TOU Record to be Returned

These are the choices:

0 = Use sequential return in the order selected
1 = Retrieve the current active record
2 = Retrieve the latest closed monthly record

13 = Retrieve the earliest closed monthly record

Waveform Log (M6 Model)

You can retrieve uncompressed waveform records by using the data table interface
and optional DeviceNet or ControlNet network communication.

Records retrieved by using the data table interface are single-cycle harmonic
magnitudes and angles from DC to the 63rd, returned as REAL values in a
sequence of data table reads and writes.

To display the record as a waveform, the returned data must be appropriately
organized by the client and an inverse FFT performed to obtain a series of time-
domain voltage and current data. That data can be plotted in a graphic format.

Waveform Data Table Retrieval

A controller or application can sequentially retrieve waveform records. Follow
these tasks in this process to retrieve waveform records.

1.

Read the number of waveform files from the Statistics.Logging table.

The Statistics.Logging table contains the following waveform information:

Element 13, the number of waveform cycles

Element 14, the number of waveform files

IMPORTANT

When using native Ethernet network communication, retrieving waveforms by
using ftp provides much faster results.

IMPORTANT

Waveform records returned through the data table interface are not
compressed.