PowerMonitor 5000 Unit Data Tables

Appendix A

7

Real

KYZ_Solid_State_Output_Scale

The KYZ output parameter divided by the scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.

1,000

1…
100,000

8

Real

KYZ_Pulse_Duration_Setting

Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: The value for delay is rounded off to the nearest 10 ms internally during
this function.

250 (ms)

0 or 50
…1000

9 Real

Output_Relay_1_Output_
Parameter

The parameter selected pulses the relay 1 output at a rate that equals the parameter
value divided by relay 1 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

0

0…6

10 Real

Output_Relay_1_Output_Scale

The relay 1 output parameter divided by the relay 1 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.

1,000

1…
100,000

11 Real

Output_Relay_1_Pulse_Duration_
Setting

Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: The value for delay is rounded off to the nearest 10 ms internally during
this function.

250 (ms)

0 or 50
…1000

12 Real

Output_Relay_2_Output_
Parameter

The parameter selected pulses the relay 2 output at a rate that equals the parameter
value divided by relay 2 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

0

0…6

13 Real

Output_Relay_2_Output_Scale

The relay 2 output parameter divided by the relay 2 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.

1,000

1…
100,000

14 Real

Output_Relay_2_Pulse_Duration_
Setting

Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: the value for delay is rounded off to the nearest 10 ms internally during
this function.

250 (ms)

0 or 50
…1000

15 Real

Output_Relay_3_Output_Paramet
er

The parameter selected pulses the relay 3 output at a rate that equals the parameter
value divided by relay 3 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

0

0…6

16 Real

Output_Relay_3_Output_Scale

The relay 3 output parameter divided by the relay 3 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.

1,000

1…
100,000

17 Real

Output_Relay_3_Pulse_Duration_
Setting

Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: the value for delay is rounded off to the nearest 10ms internally during
this function.

250 (ms)

0 or 50
…1000

Table 56 - Configuration.System.General Data Table

Element
Number

Type

Tag Name

Description

Default

Range