Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 264

Advertising
background image

264

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

13

Real

Hysteresis 17

The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).

0

0…10,000,000

14

Real

Assert Delay
Seconds 17

The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.

0

0.000…3600

15

Real

Deassert Delay
Seconds 17

The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.

0

0.000…3600

16

Real

Parameter
Selection 18

Selection of the input parameter from the

Setpoint Parameter Selection List

.

0

0…105

17

Real

Input Reference
Selection 18

Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value

0

0

18

Real

Test Condition 18

0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals

0

0…3

19

Real

Evaluation Type
18

0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)

0

0…3

20

Real

Threshold 8

The value, percent, or state that triggers the output action.

0

-10,000,000…
10,000,000

21

Real

Hysteresis 18

The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).

0

0…10,000,000

22

Real

Assert Delay
Seconds 18

The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.

0

0.000…3600

23

Real

Deassert Delay
Seconds 18

The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.

0

0.000…3600

24

Real

Parameter
Selection 19

Selection of the input parameter from the

Setpoint Parameter Selection List

.

0

0…105

25

Real

Input Reference
Selection 19

Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value

0

0

26

Real

Test Condition 19

0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals

0

0…3

27

Real

Evaluation Type
19

0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)

0

0…3

28

Real

Threshold 19

The value, percent, or state that triggers the output action.

0

-10,000,000…
10,000,000

29

Real

Hysteresis 19

The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).

0

0…10,000,000

30

Real

Assert Delay
Seconds 19

The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.

0

0.000…3600

31

Real

Deassert Delay
Seconds 19

The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.

0

0.000…3600

Table 68 - Configuration.Setpoints_16_20 Data Table

Element
Number

Type

Tag Name

Description

Default

Range

Advertising