Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 310

Advertising
background image

310

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

7

Int16

Event 1 Severity

Severity data for Events 1…6:
0x00 = Minor, recoverable
0x10 = Minor, unrecoverable
0x20 = Major, recoverable
0x30 = Major, unrecoverable

-

0x00…0x30

8

Int16

Event 1 Code

Event code for Events 1…6:
10h Generic Error
20h Current
21h Current, device input side
22h Current, inside the device
23h Current, device output side
30h Voltage
31h Mains Voltage -
32h Voltage inside the device
33h Output Voltage
40h Temperature
41h Ambient Temperature
42h Device Temperature
50h Device Hardware
60h Device Software
61h Internal Software
62h User Software
63h Data Set -
70h Additional Modules
80h Monitoring
81h Communication
82h Protocol Error
90h External Error
F0h Additional Functions

-

0x10…0xF0

9

Int16

Event 2 Severity

-

0x00…0x30

10

Int16

Event 2 Code

-

0x10…0xF0

11

Int16

Event 3 Severity

-

0x00…0x30

12

Int16

Event 3 Code

-

0x10…0xF0

13

Int16

Event 4 Severity

-

0x00…0x30

14

Int16

Event 4 Code

-

0x10…0xF0

15

Int16

Event 5 Severity

-

0x00…0x30

16

Int16

Event 5 Code

-

0x10…0xF0

17

Int16

Event 6 Severity

-

0x00…0x30

18

Int16

Event 6 Code

-

0x10…0xF0

19 … 29

Int16

Reserved

Future Use

0

0

Table 118 - Status.OptionalComm Data Table

Element
Number

Type

Tag Name

Description

Units

Range

Advertising