Snapshot Log

The Snapshot log captures a record of all data from a single cycle on command.

Setup

The Snapshot log requires the following to be configured:

Basic Metering setup

Date and Time setup

Operation

The Snapshot log captures and records the present cycle's data when a command
is issued. The data is stored in a file that contains the following parameters:

Date and time stamp to the millisecond

All metering data

All harmonic data

Single harmonic results, DC up to the 63rd for the following:

Voltage channels and average

Current channels and average

Real, reactive and apparent power per phase and total

The file name includes the local date and time stamp. Subsequent metering data
snapshot commands overwrite the previous file.

File Name

The snapshot log file name is
Metering_Snapshot_YYYYMMDD_hhmmssmmm.csv, where:

YYYYMMMDD = Year, month and day

hhmmssmmm = Hour, minute, seconds and milliseconds

Metering Snapshot Log Results

The metering snapshot log results can be retrieved from the PowerMonitor 5000
web page or ftp server. Records are also retrieved sequentially starting from the
beginning of the file by using the data table interface.