Configuration.system.general – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 248

Advertising
background image

248

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

Configuration.System.General

Table 55 - Table Properties

CIP Instance Number

803

PCCC File Number

F12

No. of Elements

50

Length in Words

100

Data Type

Real

Data Access

Read/Write

Table 56 - Configuration.System.General Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Real

Log_Status_Input_Changes

0=Disable recording of status input changes into the event log
1=Enable recording of event input changes into the event log

0

0…1

1

Real

Use_Daylight_Savings_Correction

0 = Disable Daylight Savings
1 = Enable Daylight Savings

0

0…1

2

Real

Daylight_Savings_Month/Week/
Day_Start

This is the day that the power monitor adds an hour to the time. This feature also
looks at Ethernet SNTP offset and corrects for Daylight Savings.
Example: 040107 = April/1st week/Saturday
Month Settings:
01 = January…
12 = December
Week Settings:
01 = 1st week…
05 = Last Week
Day of the Week Settings:
01 = Sunday…
07 = Saturday

030201 March,
2nd, Sunday

010101

120507

3

Real

Hour_of_Day_Start

The hour of day the daylight savings adjustment is made to add an hour.

2

0…23

4

Real

Return_from_Daylight_Savings_
Month/Week/Day

This is the day that the power monitor subtracts an hour from the time. This feature
also looks at Ethernet SNTP offset and corrects for the return from Daylight Savings.
Month Settings:
01 = January…
12 = December
Week Settings:
01 = 1st week…
05 = Last Week
Day of the Week Settings:
01 = Sunday…
07 = Saturday

110101
November, 1st,
Sunday

010101

120507

5

Real

Hour_of_Day_End

The hour of day the daylight savings adjustment is made to subtract an hour.

2

0…23

6 Real

KYZ_Solid_State_Output_
Parameter

The parameter selected pulses the KYZ output at a rate that equals the parameter
value divided by KYZ scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

0

0…6

Advertising