Command.controller_interface – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 326
326
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
Command.Controller_Interface
Table 131 - Table Properties
CIP Instance Number
839
PCCC File Number
N48
No. of Elements
16
Length in Words
16
Data Type
Int16
Data Access
Write Only
Table 132 - Command.Controller_Interface Data Table
Element
Number
Type
Tag Name
Description
Default
Range
0
Int16
Controller_Command_Word
Bit 0 = When this bit is written to the power monitor it signals the end of the demand period.
The power monitor resets the bit to 0 and sends the end of demand broadcast to all of the
slaves configured for the master/slave demand system. The power monitor must be
configured as a ‘Master’ for external demand pulse input.
Bit 1…Bit 15 = Reserved
0
0…1
1…15
Int16
Reserved
Future Use
0
0